Cable Voltage Drop: Formulas, Worked Examples, and Sizing Checks

Calculate cable voltage drop using DC and AC formulas, real cable resistance, and worked examples. Set a voltage budget to check cable length and conductor size.

Cable voltage drop: an illustrative 24 V DC source supplies about 23.07 V at the load after a 0.93 V conductor loop drop.
On this page

On this page

Engineering guide

When current flows through a cable between a power source and a load, the resistance—and in AC circuits, inductive reactance—of the conductors produces a voltage drop along the path. In a DC circuit, voltage drop follows ΔV=I×Rloop: for a two-wire run built with two identical conductors of one-way length L and single-conductor resistance per meter r, current travels L meters to the load and L meters back, making the total loop resistance Rloop=2×L×r.

For steady-state AC circuits, the calculation must match the supply configuration (×2 for single-phase or ×3 for balanced three-phase line-to-line) and account for conductor resistance R, reactance X, and load power factor (cosφ). Whether the resulting load-end voltage is acceptable depends on the voltage budget between your chosen reference terminals—comparing the estimated terminal voltage against the equipment's minimum allowable input voltage after accounting for series connector, fuse, and switch losses.

Choosing the voltage drop formula

Selecting the right equation starts with verifying how cable length and resistance are defined in your specifications. Mixing up one-way routing distance with round-trip conductor path length, or multiplying a pre-tabulated circuit factor a second time, will skew the result.

One-way length vs. complete loop resistance

When you specify a 10 m two-conductor cable assembly, 10 m is the one-way physical distance (L) from the source to the load. Electrically, current must flow out through the supply conductor and return through the return conductor to complete the circuit, as explained in the Victron Energy Wiring Unlimited guide.

For a two-wire circuit using two identical conductors of one-way length L (in m) and single-conductor resistance r (in Ω/m), the complete conductor loop resistance is:

Rloop=2×L×r

If the positive and negative conductors follow routes of different lengths or use different wire cross-sections, calculate the resistance of each wire leg separately and sum them:

Rloop=(L1×r1)+(L2×r2)

Check whether the stated value in your reference document is single-conductor resistance or loop resistance before multiplying by 2. Cable datasheets typically list resistance per individual core (Ω/1000 ft, Ω/km, or mΩ/m), which requires multiplying by 2 for an equal-leg two-wire loop. If a table already specifies loop resistance for a pair, use that value directly.

Along an assembled circuit, bulk wire is not the only series resistance. Crimp terminations, mated connector contacts, fuses, and switches add voltage loss along the path:

ΔVtotal=(I×Rloop)+ΔVother

In low-voltage circuits with tight margins, include connector contact resistance and protection elements in the path budget alongside the conductors. For how contact resistance is evaluated separately from bulk wire resistance, see Connector Resistance & Hipot Tests.

A ten meter cable contains twenty meters of conductor in a two-wire DC loopOne cable run. Two current paths.DC sourceLoad+−+−Outgoing conductor · 10 mReturn conductor · 10 mSame current in both coresL = 10 m one-wayRloop = (10 m × r) + (10 m × r) = 2Lr
Two equal ten meter conductors complete the DC current loopTwo current pathsDC sourceLoad+−+−10 meach coreL = 10 mone-wayRloop = 2 × 10 m × r
In a two-wire DC run, both cores contribute resistance. A 10 m one-way cable therefore contains a 20 m conductor loop.

DC, single-phase AC, and three-phase AC equations

In the DC equation below, I is current in amperes (A), L is one-way cable length in meters (m), and r is single-conductor resistance in ohms per meter (Ω/m):

ΔV=IRloop=2ILr

The final form applies to two equal conductors.

In the steady-state AC equations below—following the conventions in the Schneider Electric Electrical Installation Guide—I is line current in amperes (A), L is one-way cable length in kilometers (km), and R and X are single-conductor AC resistance and inductive reactance in ohms per kilometer (Ω/km) at the applicable operating conditions. These expressions apply to approximate sinusoidal steady-state conditions with a lagging (inductive) power factor cosφ, where φ is the phase angle between voltage and current and sinφ=1–cos2φ (leading capacitive loads cannot simply use +sinφ, and unbalanced three-phase or non-sinusoidal currents require matching circuit models):

  • Single-Phase AC (Two Matching Conductors):
ΔU≈2IL(Rcosφ+Xsinφ)
  • Balanced Three-Phase AC (Line-to-Line):
ΔU≈3IL(Rcosφ+Xsinφ)

When applying the AC equations, keep three rules in mind:

  1. Matched Conductor and Operating Data: Use R and X values matched to the conductor size and operating condition rather than substituting a bare DC resistance figure for the entire (Rcosφ+Xsinφ) term. Whether X is negligible depends on the specific cable's R and X values and the load power factor. The single-phase equation assumes matching outgoing and return conductors; unequal legs require summing their individual impedances.
  2. Three-Phase Factor (3): The 3≈1.732 factor gives the line-to-line voltage drop in a balanced three-phase system. Do not multiply a balanced three-phase calculation by 2.
  3. Percentage Voltage Drop Reference: Divide ΔU by the nominal supply voltage across the corresponding terminals—use the line-to-line supply voltage (such as 400 V) for balanced three-phase line-to-line drop, and the single-phase supply voltage across that conductor pair for single-phase drop:
ΔU (%)=ΔUVsupply×100%

If a load (such as a regulated DC-DC converter or switch-mode power supply) maintains approximately constant electrical input power Pin at its input terminals within its regulated operating range, a drop in terminal voltage increases its input current draw according to I≈Pin/Vload. Here Pin is the electrical input power at the load terminals (including converter efficiency, not the downstream output power Pout alone). When voltage drop is significant, check the device's input current specification at the reduced terminal voltage rather than relying on Pin/Vnominal.

Tabulated voltage drop factors

Manufacturer catalogs and installation guides often publish a voltage drop coefficient K for a given cable construction, installation method, operating temperature, circuit type, and power factor. Because K already embeds the 2 or 3 circuit multiplier and the (Rcosφ+Xsinφ) impedance term, you simply multiply K, current, and one-way length—without multiplying by 2 or 3 again.

With current I in amperes and the result ΔU in volts, match the length unit to the unit of K:

  • When K is given in V/A/km and one-way length L is in km:
ΔU=K×I×Lkm
  • When K is given in mV/A/m and one-way length L is in m:
ΔU=K×I×Lm1000

Although 1 mV/A/m equals 1 V/A/km numerically, mV/A/m is a voltage drop factor for those specified conditions (not a loop resistance), and the /1000 conversion is required when length is entered in meters.

Reading resistance from a cable datasheet

Translating a cable datasheet entry into Ω/m or Ω/km requires checking the unit, tolerance type, reference temperature, and conductor row before starting the calculation.

Converting resistance units

Because 1000 ft=304.8 m, convert single-conductor resistance from Ω/1000 ft to ohms per meter (Ω/m) by dividing by 304.8:

r (Ω/m)=DCR in Ω/1000 ft304.8

In metric specifications, resistance is typically listed in Ω/km or milliohms per meter (mΩ/m). Because 1 Ω=1000 mΩ and 1 km=1000 m, these two units are numerically identical:

1 mΩ/m=0.001 Ω/m=1 Ω/km
Resistance unit conversion
Datasheet Unit To Get Ω/m To Get Ω/km (or mΩ/m)
Ω/1000 ft Divide by 304.8 Divide by 0.3048
Ω/km Divide by 1000 Same numerical value (1 Ω/km=1 mΩ/m)
mΩ/m Divide by 1000 Same numerical value (1 mΩ/m=1 Ω/km)

Nominal values, reference temperature, and stranding

Check three specification details alongside the DCR number:

  1. Nominal (Nom.) vs. Maximum (Max.) DCR: Control and instrumentation cable datasheets often publish a nominal DCR rather than a guaranteed maximum. Nominal DCR provides a baseline estimate, whereas worst-case margin verification requires checking maximum DCR limits. For how nominal and maximum parameters are presented on component datasheets, see How to Read a Connector Datasheet.
  2. Reference Temperature: Copper resistance increases with temperature. Check whether the DCR row states a reference temperature (such as 20°C). If no reference temperature is stated in that field, note the omission rather than assuming 20°C or borrowing an ambient temperature figure from an adjacent ampacity row (such as 30°C). High ambient temperatures or heavy current loading require temperature correction for worst-case checks.
  3. Stranding and Plating: Cables of the same AWG or mm2 size can differ in DCR due to stranding construction (for instance, 16×30 stranded vs. solid conductor), lay length, and tinned vs. bare copper plating. Pull DCR from the specific cable datasheet rather than a generic wire-gauge table.

Conductor DCR vs. shield DCR

Shielded cables list electrical parameters for both the insulated cores and the shield. On the Belden 8760 Technical Data Sheet, Conductor DCR appears right above Nom. Outer Shield DCR. In a two-conductor shielded control cable like Belden 8760, the two insulated copper cores carry the circuit current while the foil shield and drain wire provide electromagnetic screening. Use Conductor DCR when calculating the supply-and-return loop resistance. For shield grounding and EMC practices, see the Cable Shielding Guide.

Worked DC and three-phase examples

The two examples below demonstrate the calculation flow for a 24 V DC control cable run and a 400 V balanced three-phase AC motor feeder. Unrounded intermediate values are retained inside the calculations and rounded for display.

24 V DC cable run with Belden 8760

The Belden 8760 Technical Data Sheet (Rev 0.667, dated 2026-02-20; product page) supplies the cable data. The operating values below are assumed for this calculation, with both insulated cores used as equal-length supply and return legs.

Cable datasheet · Belden 8760

7.06 Ω/1000 ft

Nominal conductor DCR

One pair · 18 AWG · 16 × 30 AWG tinned copper
Reference temperature is not stated in the DCR field.

Assumed operating values

DC supply
24 V
Steady current
2 A
One-way length
10 m
  1. Convert single-conductor DCR:
    r=7.06 Ω304.8 m≈0.02316 Ω/m
  2. Calculate the two-wire loop resistance:
    Rloop=2×10 m×7.06304.8 Ω/m≈0.4633 Ω
  3. Calculate conductor voltage drop:
    ΔV=2 A×20 m×7.06304.8 Ω/m≈0.93 V
  4. Find percentage drop and load voltage:
    Drop %=0.926509… V24 V×100%≈3.86%
    Vload≈24 V–0.93 V=23.07 V

Because voltage drop scales linearly with length at constant current, halving the one-way run to 5 m halves the conductor drop to ≈0.46 V. To complete the circuit verification, check the load's minimum required input voltage (Vload,min) and account for series connector/fuse drops, supply output tolerance, and operating temperature rise.

400 V three-phase motor feeder

This published example from the Schneider Electric Electrical Installation Guide (Fig. G30 / Example 1) evaluates a 400 V balanced three-phase motor fed through a 35 mm2 copper cable with a one-way length of L=50 m=0.05 km, using K (V/A/km) from the guide's copper, balanced-three-phase columns. The running and starting coefficients correspond to the power factors shown below:

Operating inputs: 400 V, 35 mm² copper, 50 m one-way
Parameter Running Starting
Line current (I) 100 A 500 A
Power factor (cosφ) 0.80 0.35
Tabulated factor (K) 1 V/A/km 0.54 V/A/km

Running:

ΔUcable,run=1 V/A/km×100 A×0.05 km=5.0 V

Starting:

ΔUcable,start=0.54 V/A/km×500 A×0.05 km=13.5 V

The upstream network also loses voltage. In Schneider's example, its running drop is 10 V at a total distribution-board current of 1000 A. During starting, the assumed upstream current is 900 A+500 A=1400 A; the guide scales the upstream drop proportionally to 14 V. The chart separates this upstream contribution from the 50 m feeder loss.

Where the voltage is lost

Running and starting voltage lossRunning: 10 V upstream plus 5 V feeder loss, 15 V total. Starting: 14 V upstream plus 13.5 V feeder loss, 27.5 V total. Both share a 0 to 30 V scale. … … 0 5 10 15 20 25 30 Running 15 V total / 3.75% 10 V 5 V Starting 27.5 V total / 6.9% 14 V 13.5 V Upstream network 50 m feeder Voltage drop (V)
Running and starting voltage lossRunning: 10 V upstream plus 5 V feeder loss, 15 V total. Starting: 14 V upstream plus 13.5 V feeder loss, 27.5 V total. Both share a 0 to 30 V scale. … … 0 10 20 30 Running 15 V total / 3.75% 10 V 5 V Starting 27.5 V total / 6.9% 14 V 13.5 V Upstream network 50 m feeder Voltage drop (V)
Both bars use the same scale. Totals include the upstream network and the motor feeder; percentages use the 400 V line-to-line supply. Source: Schneider Electric, Fig. G30 / Example 1, linked above.

Even though starting current is 5× the running current (500 A vs. 100 A), the drop in power factor from 0.80 to 0.35 changes K from 1 V/A/km to 0.54 V/A/km, yielding a 13.5 V feeder drop rather than 25 V. Running and starting conditions must therefore be calculated separately using their respective current and power factor, and compared against the equipment manufacturer's allowable input/starting voltage limits and the governing installation standard.

From voltage drop to a usable cable specification

Once you can calculate voltage drop for a given cable, the same relationships let you establish an allowable voltage budget, back-calculate maximum cable length or minimum conductor cross-section, and verify performance under load.

Setting a circuit voltage budget

Commonly cited limits such as 3% (lighting) and 5% (other uses)—as summarized in the Schneider Electric guide to IEC 60364-5-52 Table G.52.1—apply to installations supplied directly from a public low-voltage distribution system under normal steady-state operation, with variations across national standards.

For a dedicated two-wire DC circuit, determine the allowable conductor voltage drop (ΔVbudget) directly from the voltage limits at your chosen reference terminals:

ΔVbudget=Vsource,min–Vload,min–ΔVother
  • Vsource,min: Minimum guaranteed output voltage at your chosen circuit origin terminals.
  • Vload,min: Minimum allowable input voltage required at the load terminals.
  • ΔVother: Series voltage losses located between those chosen origin terminals and the load terminals that are not part of the cable conductor calculation (connectors, inline fuses, switches). If Vsource,min is already defined at terminals downstream of earlier distribution drops, do not subtract upstream drop again.

At nonzero current, if ΔVbudget≤0, no positive cable length can satisfy the budget without raising the minimum source voltage, reducing series component losses, or selecting equipment with a wider input range. If Vload,min is unknown, report the estimated drop and load voltage as outputs without assigning a pass/fail result.

Solving for maximum length or conductor area

With a positive conductor budget ΔVbudget for an equal-leg two-wire DC run, rearrange ΔVbudget=2×I×Lmax×r to solve for the maximum one-way length:

Lmax=ΔVbudget2×I×r

Using the 2 A current and Belden 8760 nominal resistance (r=7.06/304.8 Ω/m) from the DC example with an assumed conductor-only budget of ΔVbudget=0.50 V gives:

Lmax=0.50 V2×2 A×(7.06304.8) Ω/m≈5.40 m

Because this 5.40 m figure is an estimate based on an assumed 0.50 V conductor budget and nominal DCR, verify final run length against maximum DCR limits and operating temperature.

When the one-way distance L is fixed on an equal-leg two-wire DC circuit made of a single conductor material, you can screen for a candidate conductor cross-sectional area using consistent units:

Amin=2ρLIΔVbudget

Use L in meters, I in amperes, and ΔVbudget in volts to obtain Amin in mm2.

Here ρ is the conductor material's resistivity (in Ω·mm2/m) at an explicitly stated material specification and operating temperature. After computing Amin, select a standard conductor size whose cross-sectional area is at least Amin (see the AWG to mm² Wire Size Chart to match metric area to AWG sizes), then pull that specific cable's datasheet DCR at the operating temperature to recalculate ΔV. For single-phase or three-phase AC feeders, verify the candidate cable using the AC equations and its corresponding R and X (or K) values from the first section.

Sizing checks beyond voltage drop

Meeting ΔVcable≤ΔVbudget satisfies the voltage-drop criterion only. Final cable selection must also verify three independent requirements:

  • Continuous Ampacity: A short run can have negligible voltage drop while still exceeding the insulation's thermal rating at high continuous current. Confirm ampacity and bundling derating at maximum ambient temperature.
  • Connector Contact Rating and Crimp Range: Moving to a larger conductor cross-section to cut voltage drop can exceed the wire gauge or insulation diameter range accepted by connector crimp barrels, contacts, or backshells.
  • Overcurrent Protection: Confirm that fuses or breakers are rated to protect the chosen conductor size.

When specifying custom assemblies on engineering drawings, stating the one-way length, operating current, and maximum allowable loop resistance alongside connector part numbers keeps electrical and mechanical tolerances aligned—see Cable Assembly vs. Wire Harness.

Measuring voltage drop under load

When checking an installed low-voltage DC circuit with a multimeter, a voltage reading with the load idle or disconnected can miss excessive path resistance. For the same resistance, lower current produces less I×Rloop loss: a reading close to source voltage at light load does not establish the voltage available at full load.

The troubleshooting procedure in the Victron SmartSolar MPPT 100/30 & 100/50 manual (§8.6.3) illustrates how to check low-voltage DC cabling under load:

  1. Operate at Full or Representative Current: In the Victron procedure, confirm that the controller is operating at full charging current before measuring. More generally, test low-voltage DC circuits under full or representative steady operating current, since light-load readings understate full-load drop.
  2. Compare Source and Load Terminals Under the Same Condition: Under that same steady current, measure the DC voltage at the source output terminals (charger battery terminals) and compare it with the voltage at the load input terminals (battery terminals).

The voltage difference between those two terminal pairs reflects the total voltage loss along the entire path between the probes, including both conductors and any inline fuses, switches, or terminal joints. Compare that difference with the allowable path budget at the measured current. These readings give the combined loss; locating a suspect termination requires separate checks of individual sections.

Back to top

Leave a Reply

Your email address will not be published. Required fields are marked *